TECHNICAL SPECIFICATION
SENSOR GATEWAY |
Display: |
OLED |
Web Server: |
HTTP/HTTPS |
Built-ln Alerting: |
Email, SNMP Traps SMS call, |
Protocols: |
SNMP VI, v2 and v3 Modbus TCP, XML |
Network: |
IPv4 at 10/100Mbps |
External Probes: |
2 Optional Probes |
Poe |
IEEE 802.3af |
Power Adapter: |
12V DC |
|
|
Operating Conditions: |
|
Temperature: |
O 0 C to 75 0C / 32 0 F to 167 0 F |
Humidity: |
<90% RH (non-codensating) |
|
|
Temperature Probe: |
|
Resolution: |
0.1 0 C / 0.180 F |
Accuracy: |
± OSC from -100 C to +850 C; ± 1 0 F from 14 0 F to 185 0 F ; |
EXPANSION HUBS |
MULTISENSOR & HUB FOR SENSOR GATEWAY |
Expansion ports for external sensor probes: |
4 digital and 1 analog sensor |
Dry contact input ports: |
8 |
Dry contact output ports: |
4 (digital sink 100mA) |
Auxillary supply: |
maximum current capacity of 500mA at 9 to 12 VDC |
Power consumption: |
650 milliWatts |
Dimensions: |
160 mm (6.3") x 165 mm (6.5") x 60 mm (2.4") |
Operating temperature
range: |
o0 c to +75 0 C (32 0 F to +1670 F) in PoE mode |
|
|
Specifications of onboard sensors: |
|
Temperature Resolution: |
0.1 0 c (0.18)0F precision |
Temperature Accuracy: |
± o.5 0 C (+/- 0.9 0 F) over o0c to +600C |
Relative Humidity
Measurement Range: |
O to 100 % RH |
Relative Humidity
Resolution or precision: |
0.1 % RH and 1 % RH |
Relative Humidity Accuracy: |
± 2 % RH between 10 % RH to 90 % RH and ± 4 % RH below 10 % RH and above 90 % RH |
Relative Humidity Long Term Stability: |
< 1 % RH/year |
Sound (db) Resolution: |
1 db precision |
Luminosity Resolution: |
0.5 Lux precision |
Vibration unit: |
G force |
Minimum value: |
1G |
MOBILE SENSOR GATEWAY |
Additional specs compared to the wired Sensor Gateway |
|
2G GSM/GPRS/EDGE: |
850, 900, 1800, 1900 MHz |
3G HSPA+: |
900, 1800, 2100 MHz |
4G LTE: |
800, 900, 1800, 2100, 2600 MHz |
SMS Alerting: |
through SIM Card |
SENSORHUB FOR SENSOR GATEWAY |
Expansion ports for external sensor probes: |
8 |
Dry contact input ports: |
4 |
Dry contact output ports: |
2 (digital sink 100mA) |
Relay outputs: |
2 (400VAC/150VDC and 200VA/192W) |
Auxillary supply: |
maximum current capacity of 500mA at 9 to 12 VDC |
Power consumption: |
650 milliWatts |
Dimensions: |
165 mm (6.5") x 95 mm (3.7") x 22 mm (0.8") |
WIRED SENSORS |
THERMAL IMAGING SENSOR |
Thermal sensitivity: |
<50 mK (0.0500 C) |
Temperature Accuracy: |
± 1 0 C from 0 0 c to +65 o c / 320 F to 1490 F |
Field Of View (FOV): |
50 0 horizontal - 63.5 0 vertical |
|
Longwave infrared, 8 µm to 14 µm |
Resolution: |
80x60 pixels |
Operability: |
>99% of non-defective pixels. Only single-pixel defects are allowed (no clusters) |
Distance: |
Can detect IR heat from up to approximately 30m/90ft |
|
|
Certified Operating temperature range: |
-10 o c to +65 O c (140 F to +1490 F) in PoE mode |
Operating humidity range: |
< 90% RH (non-condensating) |
Dimensions: |
74 mm (2.9") x 66 mm (2.59") x 22 mm (0.8 11 ) Orange metal case with status led |
TEMPERATURE & HUMIDITY SENSOR |
Temperature Specs: |
|
Resolution: |
0.10 c / 0.180 F |
Range: |
00 to 700 C/ 14 O F to 1850 F |
Accuracy: |
± 0.5 oc from OOC to +600C± 10 F from 140 F to 1850 F |
|
|
Humidity Specs: |
|
Resolution: |
0.1% RH |
Range: |
O % to 100% RH |
Accuracy: |
± 2 between 10% and 90% RH ± 4% <10% and ) 90% RH |
SMOKE SENSOR |
Photoelectric smoke detection |
Built-in Drift Compensation Reduces False Alarms |
Self-diagnostics Meets NFPA 72 Sensitivity Testing Requirements without the Need for External Meters |
AC POWER FAILURE SENSOR |
Provides a ON/OFF indication in SensorGateway |
Delivery Period: |
30 days upon issuance of Purchase Order |